When selecting a pressure switch, don't rush to look at the measurement range

The range of a pressure switch is merely a prerequisite for entry-level applications. What truly determines its long-term stability and reliability are medium compatibility, electrical interface, and setting method. Align these three aspects first, and then revisit the range and price considerations.

上海麒诺技术团队
· About 5 min read

Core Summary

The range of a pressure switch is merely a starting point. What truly determines its long-term stability and reliability are medium compatibility, electrical interface, and setting method. Align these three aspects first, and then revisit the range and price. Doing so can save considerable costs associated with subsequent replacements and downtime.

1. The medium determines the material of the sensing element

Whether it's a diaphragm or a piston, the choice is not random

When the medium being measured is clean and has low corrosivity, the diaphragm switch responds sensitively with good repeatability, making it suitable for low pressure and differential pressure scenarios. When the medium is viscous, contains particles, or has high pressure, the piston structure is more resistant to impact and has a longer lifespan. Bailey & Mackey's Type 1381 series adopts a diaphragm structure, while Type 1581 follows the piston route, each corresponding to different working conditions.

The materials of wet components need to be reviewed

Stainless steel wetted parts are a common requirement in industrial sites, but whether it's 304 or 316 depends on whether the medium is weakly corrosive. Choosing the wrong material can lead to corrosion pits on the wetted surface after a few months, and the switching action point may drift, often necessitating a complete replacement.

II. Do not modify the electrical interface on-site

Normally open and normally closed states, as well as wiring configurations, are determined in advance

Many buyers only consider whether the switch output is SPDT or DPDT, yet overlook whether the wiring terminal is a DIN plug, cable outlet, or terminal strip. Once the interface of the on-site PLC cabinet is finalized, making temporary wiring changes is both labor-intensive and prone to leaving hidden dangers. Bailey & Mackey offers a variety of switches with different electrical connection options. Before ordering, send a photo of the control cabinet interface to the supplier for verification, which is much cheaper than reworking afterwards.

The load type determines the contact capacity

When directly using solenoid valves or motor starters and only providing input signals to PLCs, the requirements for contact capacity vary significantly. If the load current exceeds the rated value of the contact, its lifespan will plummet. It is essential to include the load type in the purchase list so that the supplier can match the appropriate switch model.

III. The Setting Method Affects Operation and Maintenance Efficiency

Fixed differential pressure or adjustable differential pressure

Some applications only require a fixed action point, while others necessitate adjusting the reset differential pressure based on season or process. Bailey & Mackey's visual setting series allows for observation of the setting position without removing the cover on-site, making it particularly suitable for pump stations and air compressor stations that require frequent inspections.

Is there any adjustment tool on site

Certain precision models require specialized tools for adjustment. If the on-site tools are incomplete, each adjustment will incur additional outsourcing services. When selecting a model, it is important to inquire whether specialized tools are required to avoid small subsequent modifications turning into significant expenses.

IV. Consider the measurement range as the last consideration

Leave sufficient overvoltage margin

Measuring range coverage of normal operating pressure is only the baseline. Water hammer, pump start-stop, and rapid valve closure can all cause transient overpressure. It is generally recommended that the operating pressure fall within the 30%–70% range of the measuring range, and it is necessary to confirm that the switches can withstand the expected transient overpressure [please verify].

Accuracy is not necessarily the higher the better

For general pump control and air compressor control, a switch with an accuracy of ±1%–±2% is sufficient; higher accuracy is only required for metering or safety interlocking. Each increase in accuracy level will result in changes to both price and lead time, so there is no need to pay for performance that is not utilized.

V. Procurement Checklist

  • Confirm the medium type, temperature, and corrosivity

  • Select the diaphragm or piston structure

  • Check the material of wet components

  • Clarify electrical interfaces, contact types, and load types

  • Confirm whether the setting method is convenient for on-site maintenance

  • The measurement range is selected based on 30%–70% of the normal pressure, leaving an overpressure margin

Parameter Table (Selection Comparison)

project

Type 1381

Type 1581

Type 3311

Note:

Sensing element

Diaphragm type [please verify]

Piston type [please verify]

Diaphragm type [please verify]

Select by medium

Applicable medium

Gas / Liquid [Please verify]

Liquid / High Pressure [Please verify]

Gas / Liquid [Please verify]

Subject to the datasheet

Wet component material

Stainless Steel [Please verify]

Stainless steel [please verify]

All stainless steel [Please verify]

Focus on verifying corrosive media

Electrical Connection

Multiple options [please verify]

Multiple options [please verify]

Multiple options [please verify]

Compatible with control cabinet

Typical Scenario

Low-pressure pump control

High-pressure hydraulics

Corrosivity / Food Grade [Please verify]

Based on operating conditions

> The above is a selection guideline. Specific parameters are subject to the original datasheet provided by Bailey & Mackey. QN TECHNOLOGY offers selection verification for models such as Type 1381, Type 1581, and Type 3311. We welcome you to send us your operating parameters for comparison.